Can the wire run that far?
Long runs lose voltage along the way. Enter the circuit details and get a voltage drop estimate in seconds — the same Rule 8-102 check an electrician runs before pulling wire to a detached garage, an EV charger, a hot tub or a shop.
Example values are loaded so you can see how it works: a 40 A EV charger, 100 ft from the panel on 6 AWG copper. Replace them with your own.
Your circuit
Your estimate
| Voltage drop | — |
| Voltage drop | — |
| Volts at the load | — |
| 3% limit (Rule 8-102) | — |
| Smallest size within 3% | — |
| Longest run at this size (3% limit) | — |
This checks one circuit against the 3% limit. The total drop from the service to the load must stay under 5% — if a feeder already uses part of that, less remains for this circuit.
Not sure your service can carry the load at all? Check the load calculator — it runs the Rule 8-200 service calculation.
More free tools: all our calculators and useful links in one place.
How the numbers work
- Formula (single-phase): voltage drop = 2 × K × amps × one-way length ÷ 1,000, with K in ohms per kilometre and length in metres. The 2 counts both conductors, out and back.
- K values: conductor resistance at 75 °C on a CEC Table D3 basis. The full table used is below.
- Limits (Rule 8-102): no more than 3% drop in any one feeder or branch circuit, and no more than 5% in total from the service to the point of use. The 3% figure is the one this page tests.
- Load: the connected load where it is known; otherwise 80% of the rating of the breaker or fuse protecting the circuit.
- Not modelled: reactance, conduit material effects, and temperature beyond the 75 °C resistance values. For larger conductors and long runs these can matter — another reason to get close calls checked properly.
- Ampacity is separate: this page checks voltage drop only. The conductor must also carry the current safely (Tables 2 and 4) and be properly protected — a wire can pass the voltage drop check and still be too small.
Conductor resistance used (Ω/km at 75 °C)
| Size | Copper | Aluminum | Size | Copper | Aluminum |
|---|---|---|---|---|---|
| 14 AWG | 10.30 | — | 1 AWG | 0.51 | 0.83 |
| 12 AWG | 6.50 | 10.40 | 1/0 AWG | 0.40 | 0.66 |
| 10 AWG | 4.07 | 6.56 | 2/0 AWG | 0.32 | 0.52 |
| 8 AWG | 2.55 | 4.13 | 3/0 AWG | 0.254 | 0.42 |
| 6 AWG | 1.61 | 2.66 | 4/0 AWG | 0.203 | 0.33 |
| 4 AWG | 1.02 | 1.67 | 250 kcmil | 0.171 | 0.28 |
| 3 AWG | 0.81 | 1.32 | 350 kcmil | 0.125 | 0.20 |
| 2 AWG | 0.64 | 1.05 | 500 kcmil | 0.089 | 0.14 |
Please read this before relying on the result
This calculator gives a screening estimate only, using the Rule 8-102 limits and conductor resistances on a Table D3 basis under the Canadian Electrical Code as adopted in BC (2024 edition). It is not a substitute for a voltage drop calculation by a qualified person, and it doesn't replace an electrical permit or inspection.
Real installations depend on conductor temperature, raceway type, power factor, and details this tool can't see. Figures may contain errors. Harbour Electrical Services Ltd. isn't liable for decisions made from these results. If the numbers are close, or before you buy wire, get the calculation checked properly — that's a free conversation, not a commitment.